Transformer impedance transformation

Impedance transformation

When a load (R) is connected to the secondary side of the transformer, depending on the turns-ratio (1:n), the effective load that appears to the source connected in the primary side can be represented as (1/n2) of the load connected to the secondary side.

This is due to the conservation of power between primary and secondary winding.

$$V_PI_P=V_SI_S$$

transformer impedance transformation 1 e1726159431825

Equivalent circuit representation

impedance transformation simple 1 e1726159464798 qu0atvizl5jeio05i38y2ml4bze46bghvfdbri8j5w

As the figure mentioned, the secondary side has load resistance of RL. Because of the power conservation on the secondary-primary side and the turns ratio, the impedance can be represented as RL/n2 in the primary side alone without having the secondary side. This is for simplify the analysis. The equivalent circuit is consistent with the following equations.

$$\cfrac{N_P}{N_S}=\cfrac{V_P}{V_S}=\cfrac{I_S}{I_P}=\sqrt{\cfrac{Z_P}{Z_S}}=\cfrac{1}{n}=\cfrac{1}{\text{Turns ratio}}$$

Example

If a transformer has a turn ratio of 1:5 (n=5) and load resistance RL=10 Ohms, then what would be the equivalent resistance seen from the primary side of the transformer?

$$\sqrt{\cfrac{Z_P}{Z_S}}=\sqrt{\cfrac{Z_P}{10}}=\cfrac{1}{5}$$

$$\implies{} Z_P=\cfrac{10}{25}=0.4\Omega{}$$

Leave a Reply

Your email address will not be published. Required fields are marked *

Quick Calculators

RC circuit
Time Constant (s) =

Cutoff Frequency (Hz) =

Time Constant (s) =

Cutoff Frequency (Hz) =

Impedance magnitude (Ω) =

Resonant frequency (Hz) =

Topics